CHECK-IT 0616  Digital Steam Trap Tester Set

Click here for a
technical drawing
of this product
THIS PRODUCT IS NO LONGER AVAILABLE The CHECK-IT Model 0616 Steam Trap Tester allows you to accurately and quickly measure pipe temperatures at the upstream and downstream sides of a steam trap. Armed with such accurate readings, you can instantly determine whether or not a steam trap is malfunctioning. With a temperature range of -100°F to 1999°F, this pocket size tester comes in a self-containing high impact case holding a quick response CHECK-IT 04260276 surface probe and a 9 volt battery. The CHECK-IT 0616 Digital Steam Trap Tester is easy to read since it incorporates a large .5" liquid crystal display which is updated 1.5 times per second. Remember . . . when a steam trap malfunctions, overall system efficiency decreases and escaping steam produces energy loss. Includes the 04260276 Surface Probe.

SPECIFICATION DATA

FEATURES

  • Built for Reliability
  • Designed especially for Steam Trap Testing
  • Readings instantaneous - NO DELAY
  • Detects malfunctioning traps instantly
  • Stainless Steel probe with 3 ft. retractable cord, for hard-to-reach areas
  • Conveniently packaged for all field use
  • ON/OFF switch recessed - No accidental turn on to waste batteries!
  • Super sensitive probe responds instantly to the hottest or coldest temperatures
  • Operates on one 9V battery, 1 year life in normal use
  • Increases efficiency and decreases energy loss
  • Large 0.5 inch LCD display: read-out visible even in direct sunlight
  • Open probe indication
  • Low battery indication
  • One full year warranty
  • Made in the United States of America

SPECIFICATIONS

Range:
-100° to 1999°F
Accuracy:
-100° to 1000°F, ±1°
Rsolution:
1°F
Repeatability:
1°F
Operating temperature:
-10° to 55°C ambient
Power:
One 9V battery, Approximately 1000 hours life
Sensor:
Type K thermocouple
Probes:
Usable to 1999°F Intermittent, 1200°F Continuous
Chord
Retractable 9 inches extends to 3 ft.
Connector:
Phono Type
Warranty:
One full year
Storage Temperature:
-20°C to 60°C at 40% relative humidity
Size:
7-1/4" x 3-5/8" x 1-1/8"
Weight:
(including battery) Approximately 10 ounces
Display:
0.5" high liquid crystal (LCD)
Case:
Drop-proof molded case

READINGS CHART

The table shows that for an upstream pressure of 150 psig, a pyrometer reading between 329°F and 348°F should be obtained. And for a down stream steam pressure of 15 psig, a pyrometer reading of between 225°F and 238°F is desirable. We can conclude, therefore, that the trap is functioning properly.


PIPE SURFACE TEMPERATURE vs. STEAM PRESSURE
Steam Pressure
(PSIG)
Steam Temp.
(°F)
Pipe Surface Temp.
(°F)
15
250
225-238
50
298
268-283
100
338
304-321
150
366
329-348
200
388
349-369
450
460
414-437



CHECK-IT 0616 SET$207.08

Surface Probe
CHECK-IT 04260276$115.47
Certification to NIST
CHECK-IT 1918$30.00